Liquid cooling / Engineering calculations

CDU Sizing for AI Data Centers: Flow, Heat and Redundancy

A 500 kW CDU is not necessarily capable of removing 500 kW under your actual water temperatures and pressure losses. Start with the heat balance, then test the hydraulic design.

Coolant distribution equipment with pumps heat exchanger and server connections
Sections in this article

A facilities team has ordered 20 new GPU racks. The vendor brochure says the coolant distribution unit (CDU) is rated at 700 kW. Is it large enough? The label is only one part of the answer. You need to know the heat entering the liquid, the supply and return temperatures, how far pumps must push the fluid and what happens when a CDU is unavailable.

This guide provides a preliminary sizing method—not a substitute for a mechanical engineer's design, server-vendor specifications or an approved commissioning plan. The useful outcome is a set of calculations and evidence requests to take into a vendor meeting.

Engineering starting pointHeat removed = mass flow × specific heat × temperature rise

Q = ṁ × cp × ΔT. Check the fluid's density and heat capacity at the actual operating temperature.

First, establish how much heat reaches the liquid

A rack's electrical nameplate rating is not necessarily the load carried by its CDU. Some servers reject heat through cold plates while fans, memory, power supplies and networking may still reject a significant share to room air. Ask the IT supplier for the liquid heat capture fraction across realistic workloads, not an assumed industry-wide 80% or 100%.

Consider an illustrative project with 20 racks at 40 kW measured IT power each. That is 800 kW of electrical input. If the server manufacturer's tested heat split puts 75% into liquid, the secondary loop must remove about 600 kW; the remaining 200 kW is a separate room-air cooling requirement. Those percentages are project assumptions, not equipment guarantees.

Total IT input800 kW20 racks × 40 kW
Liquid circuit600 kW75% of the example load
Room-air share200 kWStill needs a cooling path

Size against the agreed design case: coincident workload, rack population, any growth allowance and credible supply-water conditions. Do not simply multiply the average utilization by the number of racks and call it a safe maximum.

Worked example: secondary flow for 500 kW

Use the same heat-capacity equation engineers use to relate flow and temperature rise. For a preliminary 500 kW secondary-liquid load, suppose the water-like fluid has a density of 0.994 kg/L, a specific heat of 4.18 kJ/(kg·K) and a design return-minus-supply temperature difference of 8°C. Confirm these properties for the actual coolant and operating conditions.

Flow in liters per minute500 × 60 ÷ (0.994 × 4.18 × 8)≈ 903 L/min

Illustrative secondary-loop requirement; roughly 239 US gallons per minute.

A temperature rise of 6°C rather than 8°C would require about 1,203 L/min for the same 500 kW, other assumptions unchanged. A smaller temperature rise can therefore increase pump and pipe requirements. It does not make the heat disappear.

Design ΔTCalculated flow for 500 kWWhat to check
6°C≈ 1,204 L/minPipe velocity, pump head, cold-plate pressure drop
8°C≈ 903 L/minExample design point and server compatibility
10°C≈ 722 L/minMaximum permissible outlet temperature and approach

The primary circuit needs its own mass and energy balance. A glycol-water mixture can have different heat capacity, density and viscosity. The primary flow should be calculated separately using vendor-verified properties and temperatures; copying the secondary flow into a purchase order is not sound engineering.

Why 903 L/min is not the end of sizing

Hydraulic resistance accumulates across the CDU heat exchanger, filter, headers, quick disconnects, distribution manifolds and server cold plates. The pump must deliver the required total flow at the actual system head. A brochure listing maximum pump flow at nearly zero resistance does not establish the working point.

Facility water system (FWS)Temperature, available flow, glycol specification
CDU heat exchanger and pumpsApproach temperature, pump curves, usable controls
Technology cooling system (TCS)Rack manifolds, hose restrictions, cold-plate flow

Check the manufacturer's rating at the actual primary inlet temperature and specified secondary supply temperature. Higher facility supply temperatures, different glycol concentrations or fouled heat exchangers can reduce transferable heat at the same nominal flow. The secondary circuit's acceptable temperature and chemistry come from the IT and CDU manufacturers and the approved project design, not an arbitrary site-wide limit.

If a pump selection is near its limit, request multiple operating points, minimum stable flow, NPSH information where relevant, filter-fouling allowances and an expansion scenario. Confirm which alarms continue operating if the supervisory BMS connection drops.

N+1 sizing: a common and expensive arithmetic error

Assume the design requires 1,500 kW of liquid heat removal and individual CDU modules are each independently capable of 500 kW at the specified design temperatures. Three such modules supply 1,500 kW only while all three work. Lose one, and the available rating falls to 1,000 kW. That is not N+1 for a 1,500 kW load.

3 × 500 kW1,000 kW after one lossInsufficient for a 1,500 kW design load
4 × 500 kW1,500 kW after one lossMeets this illustrative capacity criterion

An alternative is three 750 kW modules: after one fails, two still provide 1,500 kW. Neither arrangement proves complete system resilience. Shared pipework, primary supply, headers, controls, power feeds, isolation valves and concurrent maintenance can defeat redundancy if they are not assessed together.

Also distinguish pump redundancy inside one CDU from independent CDU redundancy. An internal standby pump does not protect against failure of the unit's shared exchanger, electrical connection or controls.

CDU supplier checklist: request evidence, not just ratings

Ask the vendor forWhy it matters
Thermal capacity at actual FWS/TCS temperaturesCatalog capacity can depend on test conditions
Pump curves at proposed coolant concentrationFlow must be available at the real hydraulic resistance
Heat-exchanger approach temperatureDetermines if secondary supply temperatures are achievable
Pressure and flow requirements per rackPrevents starving some cold plates while others over-circulate
Approved materials and coolant chemistryProtects seals, metals, warranties and equipment cleanliness
Single-failure and maintenance scenariosTests system-level redundancy rather than nameplate addition
FAT, SAT and integrated testing evidenceConfirms installed performance and recovery behavior

The ASHRAE Handbook's data center chapter distinguishes the facility water system from the technology cooling system and describes how CDU heat exchangers link the two. Use that division when writing requirements, ownership boundaries and commissioning checks.

Decision to take away: approve a CDU selection only after its thermal rating, flow/head operating point, coolant compatibility and capacity after an expected failure have been demonstrated for the actual rack design.

Sources and further reading

Primary frameworks and reference materials. Engineering decisions require site-specific validation; legal classifications require assessment of the actual use case.